CapacitanceRemote Housing for High Temp, Vibration, Hazardous Areas
The Pro Remote capacitance sensor features remote electronics located in a housing that is separated from the probe making it suitable for high temperature, high vibration, or hazardous environments. It is CSA Class II listed and allows for the electronics to be installed up to 75 feet from the sensing probe and the hostile conditions, depending on the required sensitivity. It offers simple, "Quick-Set" calibration and adjustable sensitivity to less than one picofarad, making it highly reliable in a variety of powders, solids, liquids and slurries.
It operates below the RF range at just 6 KHz – unlike competitive products that operate at 9 KHz or greater – so there is no interference to compete with two-way radios or other plant equipment. An LED on the electronics housing remotely indicates there is material in contact with probe. The PRO-Shield feature protects against false readings due to coating or material buildup on the probe, while an adjustable time delay of .25 to 10 seconds can be set to ensure the most accurate readings.
Features- Point level detection and process control for solid, liquid and slurry materials
- Used in bins, vessels, tanks, chutes, and conveyorswith high vibration/ temp conditions
- Electronics can be located 75 ft. from sensing probe
- Plastics, chemicals, coal/ fly ash, concrete, food ingredients, pharmaceuticals, feed/grain, mining, etc.
- Quick-Set simple calibration
- Unsurpassed sensitivity 0.5pF
- PRO-Sheild compensates for material build-up
- Operates belowRF range, temperature stable calibration
- Fail-safe, switch selectable high/low
- Adjustable time delay to 10 seconds
- Optional sensing probes
- Internal LED indicates material in contact w/ probe
|
General Specifications
Power Requirements |
115.230 VAC, 50/60 Hz +/- 15%, 5 VA |
Output Relay |
DPDT 10 Amp at 250 VAC |
Ambient Temperature |
-40F to 185F (-40C to 85C) |
Process Temperature |
To 250F Delrin probe(121C); to 500F Teflon probe((260C) |
Pressure |
500 PSI |
Approvals & Certifications |
CSA listed Intrinsically Safe, NEMA 4X, 5 & 12 |
Probe Enclosure |
Die cast aluminum, USDA approved powder coat finish |
Electronic Enclosure |
Polycarbonate or aluminum |
Mounting |
1-1/4 NPT or 3/4 NPT 316 SS |
Standard |
1-1/4 NPT 316 SS & sanitary flange optional |
|