HOME > 1000 Series

1000 Series
Providing a dependable solution for hazardous area protection. Class 1 or Class 2 approval (depending on size)

Model 1001A is an enclosure pressurization or purging system that operates on a supply of compressed instrument air or inert gas. It regulates and monitors pressure within
sealed (protected) enclosure(s), in order to prevent combustible dust accumulation or remove and prevent flammable gas or vapor accumulations. In Class II areas,
the system maintains a "safe" (1.0") pressure. In Class I areas, the system accomplishes four air exchanges and maintains a "safe" (0.25") pressure. These processes
reduce the hazardous (classified) area rating within the enclosure(s), in accordance with the NEC - NFPA 70, Article 500, NFPA 496 and ISA 12.4.


  • UL, cUL & FM classified
  • Conforms to NFPA 496 & ISA 12.4 standards
  • Can be used on Enclosure volumes up to 450 cu. ft